Sabroe | |
Refrigeration Plant
Computation | |
Version
20.03 |
File |
: |
Holbaek |
Ref |
: |
ALB |
Page : |
1 | |
Date |
: |
2010/09/07 |
Time |
: |
14.11.01 |
|||
User |
: |
YORK REGION OST -
ROSKILDE | ||||||
Prog |
: |
COMP1/204514 |
Print |
: |
MIE ver.
6.0.2900.5512 |
SINGLE STAGE COMPRESSOR |
|
|
|
total cooling capacity | 732.4 | kW | total shaft power req. | 73.3 | kW | ||||
total heating capacity |
806. |
kW | cooling cap./shaft power ratio | 9.99 | |||||
cooling cap./line power ratio | 9.20 |
equipment for head cooling | water | ||||||||||||||
equipment for oil cooling | included | ||||||||||||||
oil separator: |
OVUR 5008HP |
motor: |
Leroy/160kW/400V/50Hz/IP23/315S/In=291A |
power line |
50 Hz - 400
V | ||||
start-up: |
star/delta |
||||||
motor eff. |
0.921 |
motor line power cons. | 79.6 | kW |
|
|
|
errors and warnings: | |
NB: chosen motor may be bigger than needed | |
NB: All data valid for fixed speed drive only ! | |
NB: design limits violation - please run Design Limits Check ! | |
Sabroe | |
Refrigerant Plant
Computation | |
Version
20.03 |
File |
: |
Holbaek |
Ref |
: |
ALB |
Page : |
2 | |
Date |
: |
2010/09/07 |
Time |
: |
14.11.01 |
|||
User |
: |
YORK REGION OST -
ROSKILDE | ||||||
Prog |
: |
COMP1/204514 |
Print |
: |
def. not
found |
Noise data - one compressor unit | |
-------------------------------- | |
Sound Power: 100.1 +/- 3 dB(A) re 10E-12 Watt | |
Mean Sound Pressure: 83.4 +/- 3 dB(A) re 2E-5 N/m2 | |
Free field over reflecting plane, dist. = 1 m | |
Ref. surface: L= 2.4 W= 1.1 H= 1.2 m | |
Frequency ---- Sound Power ---- Mean Sound Press. | |
. Compr. Motor Total Total | |
. Hz dB dB dB dB | |
63 90.2 86.6 91.8 75.1 | |
125 95.2 93.6 97.5 80.8 | |
250 91.2 91.6 94.4 77.7 | |
500 91.0 87.6 92.7 76.0 | |
1k 94.7 93.6 97.2 80.5 | |
2k 91.5 84.6 92.3 75.6 | |
4k 86.2 87.6 90.0 73.3 | |
8k 77.5 73.6 79.0 62.3 | |
dB(L) 100.7 99.0 103.0 86.3 | |
dB(A) 98.0 96.0 100.1 83.4 | |
Motor: 160.0 kW - IP23 - pole: 4 - 50 Hz - Leroy-P-315S | |