Sabroe |
Refrigeration Plant
Computation | |
Version
20.03 |
File |
: |
Holbaek |
Ref |
: |
ALB |
Page : |
1 | |
Date |
: |
2010/09/07 |
Time |
: |
13.36.40 |
|||
User |
: |
YORK REGION OST -
ROSKILDE | ||||||
Prog |
: |
COMP1/204514 |
Print |
: |
MIE ver.
6.0.2900.5512 |
SINGLE STAGE COMPRESSOR |
|
|
|
total cooling capacity | 589.5 | kW | total shaft power req. | 134.1 | kW | ||||
total heating capacity |
716. |
kW | cooling cap./shaft power ratio | 4.40 | |||||
cooling cap./line power ratio | 4.11 |
equipment for head cooling | water | ||||||||||||||
equipment for oil cooling | included | ||||||||||||||
oil separator: |
OVUR 5008HP |
motor: |
Leroy/160kW/400V/50Hz/IP23/315S/In=291A |
power line |
50 Hz - 400
V | ||||
start-up: |
star/delta |
||||||
motor eff. |
0.934 |
motor line power cons. | 143.5 | kW |
|
|
|
errors and warnings: | |
NB: All data valid for fixed speed drive only ! | |
NB: design limits check OK | |
![]() |
Sabroe |
Refrigerant Plant
Computation | |
Version
20.03 |
File |
: |
Holbaek |
Ref |
: |
ALB |
Page : |
2 | |
Date |
: |
2010/09/07 |
Time |
: |
13.36.40 |
|||
User |
: |
YORK REGION OST -
ROSKILDE | ||||||
Prog |
: |
COMP1/204514 |
Print |
: |
def. not
found |
Noise data - one compressor unit | |
-------------------------------- | |
Sound Power: 100.7 +/- 3 dB(A) re 10E-12 Watt | |
Mean Sound Pressure: 84.0 +/- 3 dB(A) re 2E-5 N/m2 | |
Free field over reflecting plane, dist. = 1 m | |
Ref. surface: L= 2.4 W= 1.1 H= 1.2 m | |
Frequency ---- Sound Power ---- Mean Sound Press. | |
. Compr. Motor Total Total | |
. Hz dB dB dB dB | |
63 91.1 86.6 92.4 75.7 | |
125 96.1 93.6 98.0 81.4 | |
250 92.1 91.6 94.9 78.2 | |
500 91.9 87.6 93.3 76.6 | |
1k 95.6 93.6 97.7 81.1 | |
2k 92.4 84.6 93.0 76.4 | |
4k 87.1 87.6 90.4 73.7 | |
8k 78.4 73.6 79.7 63.0 | |
dB(L) 101.6 99.0 103.5 86.8 | |
dB(A) 98.9 96.0 100.7 84.0 | |